RMMV Series
Rack Mount AC/DC Power Supply
Operating and Installation Instructions
52-391 Rev A.02
Zobrazit stránku 0
1 2 3 4 5 6 ... 19 20

Shrnutí obsahu

Strany 1 - RMMV Series

RMMV SeriesRack Mount AC/DC Power SupplyOperating and Installation Instructions52-391 Rev A.02

Strany 2

4.2 Wiring4.2.1 Wire RoutingAll wiring must be installed in accordance with NFPA70 [NEC760] and all local coderequirements.Power Limited wiring requi

Strany 3 - Table of Contents

Section 5Operating the RMMV Rack Mount Power Supply5.1 Jumper Configuration5.1.1 AC ZonesEach individual AC output zone may be configured for a 24VAC

Strany 4 - Introduction

VOLTAGESELECT24V12VBATDETECTEARTH GNDDETECTAC ONOUTPUT VOLTAGESELECT SWITCHEARTH GOUNDDETECTION ENABLEBATTERY PRESENCEDETECTION ENABLEAC PRESENCEVISUA

Strany 5 - Section 2

5.1.2.1.2 SPS4 Jumper SettingsThe SPS4 has two jumpers for setting its output voltage. It is factory set for 12VDC out. Ifa different voltage is req

Strany 6 - System Overview

5.2.2.1.3 AC FLT This LED illuminates when the AC input voltage falls below approximately 85% of thenominal input voltage setting.5.2.2.1.4 COM FLT Th

Strany 7 - Figure 3.2.1

5.3 TroubleshootingWARNING - Installation and service should only be performed by a qualified service person andshould conform to all local codes5.3.1

Strany 8

Contact AlarmSafInternal problemVerify correct setting of Bat DetectjumperBat Detect Jumper (JP10) setincorrectly on the internal PS5-MVerify connecti

Strany 9 - Installation

Section 6Specifications6.1 Electrical Specifications6.1.1 Input Voltage 120VAC nominal6.1.2 Input Power 504W Max 6.1.3 Input Frequency 50-60Hz6.1.4 Mi

Strany 10 - AlarmSaf

Wiring and using an RMBE Series Battery Enclosure with the RMMVThe RMBE Series of Battery Enclosures provides battery backup in a standard 19 inch 2RU

Strany 11 - Section 5

OFFRESETONAC POWERTo reduce the risk of fire, replace interiorfuses only with same type and ratingRISK OF ELECTRICAL SHOCKDO NOT OPENAlarmSaf www.ala

Strany 12 - Page 12 of 20

Warnings and NoticesWARNING - To reduce the risk of fire or electric shock, do not expose this productto rain or moistureWARNING - This installation

Strany 13 - Page 13 of 20

GlossarySplitting a bulk power supply output into multiple, current limited outputs to prevent asingle circuit failure from talking down an entire sys

Strany 14 - Page 14 of 20

Table of Contents20Glossary18Wiring and using an RMBE Series Battery Enclosure with the RMMVAppendices:176.3 Mechanical Specifications176.2 Temperatur

Strany 15 - 5.3 Troubleshooting

Section 1IntroductionThe RMMV series of rackmount power supplies provides either 24 or 28 VAC for powering CCTV orsimilar low voltage AC operable equi

Strany 16 - Page 16 of 20

Section 2Applicable Standards / DocumentsNFPA StandardsNFPA 72 National Fire Alarm CodeNFPA 70 National Electrical CodeUS StandardsUL 294 Access Contr

Strany 17 - Specifications

Section 3System Overview3.1 Electrical Ratings and SpecificationsManufactured ByAlarmSaf65A Industrial WayWilmington, MA 01887Tel: 800 987 1050 978

Strany 18

3.2 Terminal DescriptionsAll terminal strips are removable with locking screws and accept wire sizes from 12-26AWG. Wireshould be sized appropriately

Strany 19 - Page 19 of 20

3.2.6 Fault Outputs (Common Fault / AC Fault) Form C Contacts Contacts rated at 1A @ 24VDC, 0.5A @ 120VAC Fault relays employ “fail-safe” operatio

Strany 20 - Glossary

Section 4Installation4.1 Mounting4.1.1 Mount the unit in locations that meet the following temperature and humidity requirements.Do not expose to cond